Ventilation of operating rooms without humidifying them?

Lüderitz, P.; Hofmann, H.; Krukowski, M.

Zeitschrift für die Gesamte Hygiene und ihre Grenzgebiete 31(7): 411-412

1985


ISSN/ISBN: 0049-8610
PMID: 4049970
Document Number: 248274
At outside temperatures as low as 0.degree. C, relative humidities not below 10 per cent were measured in two different operating rooms during surgical treatment which involved an air exchange of 15 to 20 times and which were not humidified. No discomfort is felt by persons present in rooms involving so low a humidity. It is proposed to do without humidification in air-conditioned rooms, because it is questionable in terms of hygiene.